Stator Current Limiter: SCL1C

 

Model Equations and/or Block Diagrams

Parameters:

TB1oel Overexcited regulator denominator lag time constant 1 (s)
TC1oel Overexcited regulator numerator lead time constant 1 (s)
TB2oel Overexcited regulator denominator lag time constant 2 (s)
TC2oel Overexcited regulator numerator lead time constant 2 (s)
KPoel Overexcited PID regulator proportional gain (pu)
KIoel Overexcited PID regulator integral gain (pu)
KDoel Overexcited PID regulator differential gain (pu)
TDoel Overexcited PID regulator differential time constant (s)
VOELmax3 Maximum OEL PID output limit (pu)
VOELmin3 Minimum OEL PID output limit (pu)
VOELmax2 Maximum OEL lead lag 1 output limit (pu)
VOELmin2 Minimum OEL lead lag 1 output limit (pu)
VOELmax1 Maximum OEL output limit (pu)
VOELmin1 Minimum OEL output limit (pu)
TB1uel Underexcited regulator denominator lag time constant 1 (s)
TC1uel Underexcited regulator numerator lead time constant 1 (s)
TB2uel Underexcited regulator denominator lag time constant 2 (s)
TC2uel Underexcited regulator numerator lead time constant 2 (s)
KPuel Underexcited PID regulator proportional gain (pu)
KIuel Underexcited PID regulator integral gain (pu)
KDuel Underexcited PID regulator differential gain (pu)
TDuel Underexcited PID regulator differential time constant (s)
VUELmax3 Maximum UEL PID output limit (pu)
VUELmin3 Minimum UEL PID output limit (pu)
VUELmax2 Maximum UEL lead lag 1 output limit (pu)
VUELmin2 Minimum UEL lead lag 1 output limit (pu)
VUELmax1 Maximum UEL output limit (pu
VUELmin1 Minimum UEL output limit (pu)
Ireset SCL reset reference, if inactive (pu)
TenOEL Overexcited activation delay time (s)
TenUEL Underexcited activation delay time (s)
Toff SCL reset delay time (s)
ITHoff SCL reset threshold value (pu)
TIQoel Overexcited reactive current time constant (s)
KIQoel Overexcited reactive current scaling factor (pu/pu)
TIPoel Overexcited active current time constant (s)
KIPoel Overexcited active current scaling factor (pu/pu)
TIQuel Underexcited reactive current time constant (s)
KIQuel Underexcited reactive current scaling factor (pu/pu)
TIPuel Underexcited active current time constant (s)
KIPuel Underexcited active current scaling factor (pu/pu)
TITscl Stator current transducer time constant (s)
ITFpu SCL thermal reference for inverse time calculations (pu)
Iinst SCL instantaneous stator current limit (pu)
IinstUEL Underexcited region instantaneous stator current limit (pu)
Ilim SCL thermal stator current limit (pu)
TAoel SCL reference filter time constant (s)
c1 SCL exponent for calculation of IERRinv1 (pu)
K1 SCL gain for calculation of IERRinv1 (pu/pu)
c2 SCL exponent for calculation of IERRinv2 (pu)
K2 SCL gain for calculation of IERRinv2 (pu/pu)
VINVmax SCL maximum inverse time output (pu)
VINVmin SCL minimum inverse time output (pu)
Fixedru SCL fixed delay time output (pu)
Fixedrd SCL fixed cooling down time output (pu)
TSCL SCL timer reference (pu)
Tmax SCL timer maximum level (pu)
Tmin SCL timer minimum level (pu)
KFB SCL timer feedback gain (pu)
SW1 OEL reference ramp logic selection (0 = fixed ramp rates - Kru and Krd, 1 = IERRinv1)
Krd SCL reference ramp down rate (pu/s)
Kru SCL reference ramp up rate (pu/s)
KZRU SCL thermal reference release threshold (pu)
TVTscl Terminal voltage transducer time constant (s)
VTmin SCLoel minimum voltage reference value (pu)
VTreset SCLoel voltage reset value (pu)
IQminOEL SCLoel minimum reactive current reference value (pu)
IQmaxUEL SCLoel maximum reactive current reference value (pu)
KPref SCL reference scaling factor based on active current (pu)